Product Portfolio

Pre-Insulated Ducts, Insulated Panels & Underdeck Insulation

Three focused product families, each purpose-built for high-performance HVAC and building thermal insulation — engineered for efficiency, durability and speed of installation.

In-house manufacturing at Shoolagiri SIPCOT, Tamil Nadu Project-specific engineering & submittal support CFC/HCFC-free insulation cores Serving projects across India

What We Manufacture

A Deliberately Focused Range

Clima Tech does not try to supply every insulation product on the market. We concentrate on three closely related families that share the same underlying technology — rigid closed-cell foam bonded to protective facings — and the same engineering discipline. That focus is what lets us hold tolerances, answer technical questions properly and support a project from specification through to handover.

ENERMAX PIR pre-insulated HVAC ductwork being installed in a commercial building

Pre-Insulated HVAC Ducts

Brand: ENERMAX PIR™

Rigid closed-cell PUF or PIR insulation faced on both sides with aluminium foil or PPGI, forming the duct wall and the insulation layer in a single panel. Factory-cut, grooved, folded and sealed for low-leakage air distribution with fewer joints and lower installed weight.

Explore duct systems
Insulated sandwich panel craned into position while installers guide it onto the frame

Insulated Wall Panels

PUF sandwich panels · 20–100 mm

Thermally efficient sandwich panels with a rigid polyurethane core bonded between PPGI or GI facings, joined by tongue-and-groove interlocking profiles. Used for industrial and commercial walls, partitions and service enclosures where speed and thermal continuity both matter.

Explore wall panels
Completed foil-faced underdeck insulation across a warehouse roof, racking below

Underdeck Insulation

PUF / PIR · 20–100 mm

Thermal insulation installed below metal roof decks to interrupt heat transfer from the roof into the occupied space. Mechanically fixed or adhesive-assisted, with aluminium foil, PPGI or tissue facing options to suit the internal finish.

Explore underdeck systems

Our Duct Brand

ENERMAX PIR™

ENERMAX PIR™ is the brand name of the pre-insulated air duct system manufactured by Clima Tech. It is a polyisocyanurate panel system: a rigid, closed-cell PIR core faced on both sides with embossed aluminium foil, supplied as 4000 × 1200 mm panels in 20 mm and 30 mm thicknesses.

Because the panel is both the duct and the insulation, one trade installs one product — there is no separate lagging operation, no fibrous material in the air path and no wrapping to be damaged by following trades.

  • 0.020 W/m·K thermal conductivity
  • EX 20P for indoor duty; EX 30P for outdoor and higher-pressure duty
  • Duct sections up to 4 m long, reducing joint count
  • CFC/HCFC-free blowing agent
Technician sealing ENERMAX PIR duct fittings on a fabrication bench
ENERMAX PIR™ duct sections and fittings, fabricated from aluminium-faced rigid PIR panel.

Side by Side

Indicative Technical Comparison

Use this table for early-stage orientation. Final selection should always be made against approved datasheets and the specific conditions of your project.

Comparison of Clima Tech product families
Parameter Pre-Insulated HVAC Ducts Insulated Wall Panels Underdeck Insulation
BrandENERMAX PIR™Clima TechClima Tech
Insulation materialPUF / PIR rigid foamPolyurethane foam (PUF)PUF / PIR
Thickness range20 / 25 / 30 mm20 mm to 100 mm20 mm to 100 mm
Thermal conductivity≤ 0.022 W/mK (0.020 W/m·K for ENERMAX PIR™)≤ 0.023 W/mKPer selected core
Facing optionsAluminium foil / PPGIPPGI / GIAluminium foil / PPGI / tissue
Jointing / fixingGrooved, folded & sealedTongue-and-groove interlockingMechanical fixing or adhesive-assisted
Primary roleHVAC air distributionBuilding envelope & partitionsRoof heat-gain control

Values are indicative — confirm against approved datasheets and project-specific engineering data. Fire, smoke, strength, water absorption and air-leakage claims are supported by the final third-party report for the relevant product.

01 How to Choose

Six Questions That Settle the Specification

Most selection decisions come down to the same short sequence. Work through it and you will have narrowed the product, the grade and the thickness before you speak to anyone.

01

Is it moving conditioned air, or holding heat out of a space?

Air distribution points to pre-insulated ductwork (ENERMAX PIR™). A building envelope or partition points to insulated wall panels. A metal roof contributing to internal heat load points to underdeck insulation. Many projects need two or all three.

02

For ductwork — indoors or outdoors?

EX 20P (20 mm) covers indoor supply, return, fresh-air and exhaust duty up to 1,000 Pa and 15 m/s. EX 30P (30 mm) is the grade for outdoor routes, higher pressures up to 1,750 Pa and velocities up to 35 m/s, with project-specific weather protection.

03

Is a fibre-free air path required?

In hospitals, cleanrooms, pharmaceutical production and food facilities the answer is usually yes. ENERMAX PIR™ has a rigid closed-cell core with aluminium on both faces, so nothing fibrous is exposed to the airstream.

04

For panels — what internal condition must the wall hold?

Work back from the temperature difference you need to maintain and the span between supports. The R-value table above converts core thickness into thermal resistance so you can size the core against the design condition rather than by habit.

05

Is the duty on our exclusion list?

Kitchen grease extract, smoke extract or fire-rated ductwork, chemical fumes, solid-particle conveying, uncontrolled process exhaust and temperatures outside the validated range are all outside the scope of our duct systems. Tell us early and we will scope our supply to the parts of the system where our product is right.

06

What do you send us?

Duct schedules with pressure classes, or elevations and spans, or roof construction and area. The more of that we have, the more specific our first response can be.

02 Thermal Performance

Conductivity Is the Material. Resistance Is the Product.

Thermal conductivity (λ) describes the foam. What a designer actually needs is thermal resistance (R) — which depends on how thick the layer is. The charts below convert our published conductivity figures into the resistance each thickness delivers.

Thermal resistance of the duct wall

Minimum R-value of the insulation layer, calculated as thickness ÷ thermal conductivity. Higher is better. ENERMAX PIR™ grades are highlighted; the general duct range is shown for context.

ENERMAX PIR™ EX 20P
1.00
ENERMAX PIR™ EX 30P
1.50
Duct panel 20 mm
0.91
Duct panel 25 mm
1.14
Duct panel 30 mm
1.36
R-value in m²K/W · bars scaled to the largest value
Wall panel thermal resistance by core thickness

Minimum R-value of the PUF core at ≤ 0.023 W/mK. Doubling the core doubles the resistance.

20 mm core
0.87
30 mm core
1.30
40 mm core
1.74
50 mm core
2.17
60 mm core
2.61
80 mm core
3.48
100 mm core
4.35
R-value in m²K/W · bars scaled to the largest value
ENERMAX PIR™ — calculated thermal resistance (λ = 0.020 W/m·K)
Core thickness R-value (m²K/W) U-value (W/m²K) R-value (imperial)
20 mm1.001.005.68
30 mm1.500.678.52

Calculated as R = thickness ÷ λ and U = 1 ÷ R for the insulation layer alone. Surface resistances, the aluminium facings and any air films are excluded, so a built-up assembly will differ. Imperial R-value in h·ft²·°F/BTU.

Insulated wall panels — calculated thermal resistance (λ ≤ 0.023 W/mK)
Core thickness Minimum R (m²K/W) Maximum U (W/m²K) R-value (imperial)
20 mm0.871.154.94
30 mm1.300.777.41
40 mm1.740.579.87
50 mm2.170.4612.34
60 mm2.610.3814.81
80 mm3.480.2919.75
100 mm4.350.2324.69

Because the published conductivity is a maximum (≤ 0.023 W/mK), the resistances above are minimums. Core layer only — facings, fixings and surface resistances excluded.

Underdeck insulation — calculated thermal resistance by core and thickness
Core thickness R with PIR core
λ 0.020 W/m·K
R with PUF core
λ 0.023 W/mK
U (PIR core)
20 mm1.000.871.00
25 mm1.251.090.80
40 mm2.001.740.50
50 mm2.502.170.40
75 mm3.753.260.27
100 mm5.004.350.20

Insulation layer only, calculated as R = thickness ÷ λ. The actual improvement to a roof depends on the existing deck construction, air films and any ventilated cavity — we will assess your roof rather than quote a generic figure.

Read these figures correctly

Every R and U figure on this page is the insulation layer in isolation, derived arithmetically from our published conductivity. A real assembly also involves surface resistances, facings, fixings, air films and any thermal bridging at supports and joints. Use these numbers to compare thicknesses and to sanity-check a selection — not as a substitute for an assembly calculation against your project’s design criteria.

03 Materials

PUF or PIR — What Actually Differs

Both are rigid closed-cell foams from the same chemical family, and the names get used loosely in the market. Here is the honest version.

PUF and PIR compared
Property PUF — polyurethane PIR — polyisocyanurate
ChemistryPolyol reacted with isocyanate at an approximately balanced indexThe same base chemistry run at a higher isocyanate index, forming isocyanurate ring structures
Cell structureRigid, closed-cellRigid, closed-cell
Thermal conductivity in our products≤ 0.023 W/mK (wall panels)0.020 W/m·K (ENERMAX PIR™ duct panel)
Thermal stabilitySoftens at lower temperatures than PIRGenerally more thermally stable; the ring structure tends to char rather than melt
Moisture behaviourClosed cells limit water uptakeClosed cells limit water uptake
Where Clima Tech uses itInsulated wall panels; available in underdeck systemsENERMAX PIR™ ductwork; available in underdeck systems

General material characteristics for orientation. Fire and smoke performance for any specific configuration is established by test, not by material family — those claims are supported by the final third-party report for the product supplied.

04 Reference

Glossary of Terms

The vocabulary used across these product pages, in plain language.

PIRPolyisocyanurate
A rigid closed-cell insulation foam produced at a high isocyanate index. The core material of ENERMAX PIR™, with a thermal conductivity of 0.020 W/m·K.
PUFPolyurethane foam
A rigid closed-cell insulation foam. The core of our insulated wall panels, with a thermal conductivity of ≤ 0.023 W/mK.
PPGIPre-painted galvanised iron
Galvanised steel with a factory-applied paint system, used as a durable, coloured, corrosion-resistant facing on panels and ductwork.
GIGalvanised iron
Zinc-coated steel sheet. Used both as a panel facing and, in conventional practice, as the material of fabricated sheet-metal ductwork.
Closed-cell foam
A foam whose cells are sealed from one another, which restricts the movement of air and moisture through the material and gives the panel its rigidity.
Thermal conductivityλ (lambda), W/m·K
How readily a material conducts heat. Lower is better. It is a property of the material, independent of how thick the layer is.
Thermal resistanceR-value, m²K/W
How well a specific layer resists heat flow, calculated as thickness divided by conductivity. Higher is better. Unlike λ, it depends on thickness.
U-valueW/m²K
The rate of heat transfer through an assembly, the reciprocal of total thermal resistance. Lower is better.
Thermal bridging
A localised path of higher heat flow through an otherwise insulated element — typically at a joint, flange, fixing or support. It undermines the performance the insulation was specified to deliver.
Vapour barrier
A layer that resists the passage of water vapour into the insulation. The aluminium facings on ENERMAX PIR™ act as a vapour-resistant skin on both sides of the core.
Air leakage
Air escaping the duct between the fan and the terminal. It wastes fan energy and starves the spaces at the end of the run. Fewer joints means fewer potential leakage paths.
Static pressurePa (pascal)
The pressure the duct wall must resist. ENERMAX PIR™ is rated to 1,000 Pa (EX 20P) and 1,750 Pa (EX 30P).
Face velocitym/s
The speed of air through the duct. Higher velocity means a smaller duct but more pressure drop and more noise. Our grades are validated to 15 m/s and 35 m/s respectively.
Sandwich panel
A composite of two metal facings bonded to an insulating core, behaving structurally as one component rather than three separate layers.
Tongue-and-groove
An interlocking edge profile in which the projecting edge of one panel seats into the recessed edge of the next, aligning the panels and maintaining insulation continuity across the joint.
Underdeck insulation
Insulation fitted to the underside of a roof deck to interrupt heat transfer from the roof into the occupied space below.
Facer
The sheet material bonded to the surface of the insulation core — aluminium foil, PPGI, GI or tissue depending on the product and the exposure.
Blowing agent
The agent that expands the foam during manufacture. Ours is CFC/HCFC-free.
Areal densitykg/m²
Weight per square metre of panel — the figure that governs handling, support spacing and the load the ductwork imposes on the structure.

Product Selection FAQs

Which product do I need for a commercial HVAC project?

For the air-distribution network itself, our pre-insulated duct system, branded ENERMAX PIR™, replaces GI ductwork plus applied insulation with a single panel. If the project also involves an industrial envelope, plant rooms or partitions, insulated wall panels cover that scope; if there is a large-span metal roof contributing significant heat gain, underdeck insulation addresses it. Many projects use two or all three.

What is the difference between PUF and PIR?

Both are rigid closed-cell polyurethane-family foams. PIR (polyisocyanurate) is produced with a higher isocyanate index, which gives it a more thermally stable, char-forming structure and, in our duct panel, a lower thermal conductivity of 0.020 W/m·K. PUF is widely used across our wall panel and underdeck ranges where thickness rather than ultimate conductivity is the main design lever.

Do you supply to projects outside Tamil Nadu?

Yes. Our manufacturing facility is at Shoolagiri SIPCOT in Tamil Nadu and our corporate and engineering office is in Chennai, and we supply projects across India. Delivery sequencing is planned with your site programme — talk to us early so fabrication and dispatch can be aligned to your installation windows.

Can you help write the specification?

Yes. We provide suggested specification wording, product datasheets and method statements, and our engineering team will review your drawings and performance requirements before recommending core, thickness, facing and jointing. See Quality & Engineering Support for how that process runs.

Let’s Build More Efficient Systems

Share your drawings, specifications or site conditions and our engineering team will recommend the right core, thickness, facing and jointing system for the project.